What Is the Difference Between Peak Shaving and Load Shifting?
Peak shaving discharges the battery to hold site demand below a ceiling. Load shifting charges in cheap hours and discharges in expensive ones. Both run on the same cabinet and the same stored energy, so they compete for it rather than stack on top of each other.
A shaving setpoint acts minute by minute. The cabinet watches the demand the site is drawing and covers the part above the ceiling. Shifting works to a timetable, charging overnight and emptying inside the tariff's expensive window.
One is a ceiling and the other is a schedule. Treating them as the same feature is the quickest way to buy a cabinet that is the wrong shape for the bill.
How Does Each One Show Up on the Bill?
Shaving shows up on the demand line, measured in kW. Shifting shows up on the energy line, measured in kWh and in the rate paid for each hour. Check which of the two carries more of your bill. The cabinet's power rating serves the first, and its usable energy serves the second.
| Bill line | What it charges for | What reduces it | Cabinet number that matters |
|---|---|---|---|
| Demand charge | the highest kW the register records | shaving, held for the whole month | power rating, 37.5 to 60 kW |
| Energy charge | kWh at the rate for that hour | shifting into cheaper hours | usable energy, 72 to 108 kWh |
| Standing charge | the connection capacity you hold | little, unless the connection shrinks | no cabinet input |
A fourth line exists on some tariffs, where exported energy is paid at a lower rate than imported energy. That line rewards self-consumption, which is shifting with a solar array doing the charging.
How Do You Work Out Which One Your Bill Rewards?
Split the annual bill into its lines and compare the demand line against the energy line. If demand is the larger share, start with shaving. If the energy line carries the bill, shifting and self-consumption move the number further. One winter bill and one summer bill is enough to see the split.
- Take two bills One from a high-load month and one from a quiet month, both with the demand register.
- Separate the lines Demand, energy, standing charge and any export credit, kept apart rather than added into one figure.
- Compare demand against energy The larger line decides whether power or energy is the constraint on the cabinet.
- Size to the winner Power rating for shaving, usable energy for shifting, and both when the two are close.
Can One Cabinet Do Both?
Yes, on the same hardware. The cabinet runs self-consumption, zero export, time-of-use arbitrage, demand-side response, emergency backup and VPP. Switching between them is a setting rather than a second product. What it cannot do is spend the same 90 kWh twice.
A site that shaves 45 kW for two hours has used the shift for that day. A second expensive window means a larger cabinet, or a decision about which window matters more. That decision belongs in the design, not in a firmware menu.
Where Do the Two Approaches Conflict?
They compete for stored energy and for the inverter's rating. A shaving setpoint can hold the battery back all morning and leave nothing for the evening window. The schedule has to state which job owns the battery in each hour, and the site has to accept the answer.
They are also scored differently. Shaving is judged against a monthly maximum, so one bad interval costs the whole month. Shifting is judged daily, so a missed evening recovers the next day. That asymmetry is why sites with a sharp, short peak usually shave.
What Do We Need to Answer This for Your Site?
Request a quote and, if you have it, twelve months of consumption, the demand register and the tariff with its time bands. Those three tell us which line is worth attacking and how much energy the window needs. Without the register, any recommendation is a guess dressed as a proposal.
The cabinet choice usually comes out smaller than the site expects once the credited kW is known. A 60 kW cabinet covers a 60 kW peak, and 150% for ten seconds covers the inrush that starts a motor.
Questions about this article
Which one is better for my bill?
The one that attacks the larger line. If the demand charge is the bigger share of what you pay, shaving returns more per kWh stored. If the energy line dominates, shifting and self-consumption return more. The demand register and the tariff settle it in one reading.
Can I switch between the two later?
Yes. Both are settings on the same cabinet, so the mode can change without new hardware. What cannot change is the power rating and the usable energy you bought, and those two set the ceiling on either strategy.
Does shaving affect production?
It should not, because the cabinet covers load rather than shedding it. The discharge is capped at the cabinet's rating and the site keeps running. Circuits that must never be interrupted belong on the essential board, which is a commissioning decision.
How much of a peak can one cabinet cover?
Up to 60 kW on the largest model, with 150% for ten seconds for motor starts. Ten cabinets in parallel reach 600 kW. Above that the site is looking at a different product class rather than a bigger order of the same cabinet.
One Bill Tells Us Which Line to Attack.
A winter bill, a summer bill and the demand register. You get a straight answer on whether power or energy is your constraint, plus the cabinet that matches it.