CabESSLuminBlock H · C&I all-in-one hybrid ESS
Home / Tools / BESS Sizing Sheet
Tool · paper method, no login

BESS Sizing Sheet

A worksheet rather than a live calculator: the arithmetic behind a first proposal, set out so you can run it on paper or in a spreadsheet. Six inputs, five steps, a worked table.

It gives a model and a count. It is an estimate, not a design, and the site survey still decides the final answer.

6 inputs, 5 steps90% usable energy200% maximum PV ratio480 kWh per system with expansion
INPUTS

Six Inputs Do Most of the Work

Size from the bill, not the datasheet. Peak kW sets the power rating; daily energy shifted between cheap and expensive hours sets capacity, at 90% usable. PV can be oversized to 200% of the inverter. Then check the site limit: one cabinet, three extra battery cabinets, or a parallel system up to ten units.

InputWhere to find itWhy it matters
Daily kWhA year of bills divided by days, or one recent billSets the energy ceiling
Maximum continuous loadHalf-hourly meter dataSets the power rating
Inrush loadMotor and pump nameplatesCovered by the 150% overload
PV kWpArray plan or existing inverterCapped at 200% of rating
Backup minutesYour own outage policyTurns into usable energy
Parallel intentGrowth planDecides one unit or several
FIVE STEPS

Five Steps in Order

  1. Power from the peak Take the highest half-hourly load. If it is above 60 kW, the unit count starts at two.
  2. Energy from the window Backup hours times the load you back up, divided by 0.9, gives the nameplate energy.
  3. Check the PV ratio Array kWp should stay at or below twice the cabinet kW rating.
  4. Pick the model Smaller of the models that covers both the power and the energy.
  5. Check the limits 480 kWh per system, ten units in parallel, then temperature and altitude.
WORKED

Three Worked Examples

InputsCabinetUsableRuntime at peak
25 kW peak, 2 h window, 30 kWp PVBES-H37.5X8072 kWh2.9 h at 25 kW
45 kW peak, 2 h window, 60 kWp PVBES-H50X10090 kWh2.0 h at 45 kW
80 kW peak, 3 h window, 100 kWp PVTwo BES-H60X120216 kWh2.7 h at 80 kW

The third row shows where parallelism starts. An 80 kW peak cannot sit under a single 60 kW inverter, so the count goes to two before the energy is considered.

OUTPUT

What the Numbers Give You

The output is a model, a unit count, and a note on whether battery cabinets are needed. From there the runtime table follows: 2, 4, 6 and 8 hours at the chosen power.

A 60 kW cabinet with one battery cabinet runs 3.6 hours at full power. With three it reaches 480 kWh, which is eight hours. Those are the two steps most sites choose between.

LIMITS

Where the Estimate Stops

Temperature, altitude and corrosion class are not in the six inputs. A site above 2,000 m, a coastal site inside one kilometre, or a plant that runs above 55 °C ambient changes the answer.

The survey covers foundation, clearances and the cable route. Those decide scope lines rather than cabinet count, and they are the ones a buyer most often forgets.

FAQ

Questions about BESS sizing sheet

Is this a design?

No. It is an estimate for budgeting and for checking a proposal. A design needs the survey, the single-line diagram and the grid application.

Why divide by 0.9?

Usable energy is 90% of nameplate because the cabinet stops at 90% depth of discharge. A 120 kWh cabinet gives 108 kWh.

What if my peak lasts minutes?

Use the half-hourly figure anyway. Short peaks are what the 150% overload for 10 s covers, and the meter settles on the half-hour.

Can I size for PV only?

Yes, but keep the array at or below 200% of the cabinet rating. More panels do not add storage, they add clipping.

How much battery storage do I need?

Start with the load you want to hold and for how long: usable kWh is kW multiplied by hours. Then add the peak you want to shave and check it against 72, 90 or 108 kWh usable and the ten-unit ceiling. The sheet works it through in five steps.

How do I calculate battery storage size?

How to calculate battery storage size: start from the load you must carry and for how long, not from a kWh number you have seen. Peak-kW x hours = kWh for backup; daily shift x usable energy = kWh for arbitrage. This sheet runs both.

How much battery storage for solar panels do I need?

How much battery storage for solar panels depends on the evening load you want to cover, not on the array size. Take the kW you need after sunset and multiply by the hours; that kWh figure, divided by 0.9, is the nominal size to price.

Run Your Figures, Then Have Them Checked

Start with the form. Our sales team asks for the six inputs and the site address. The reply marks where the estimate holds and where the survey would move it.