The Grid Voltage Sets the Design
The LatAm line runs at 208/220 V, 50/60 Hz, with three MPPTs and 30 or 35 kW, in 80–120 kWh enclosures. It is a separate product family with its own datasheet and cannot be mixed with the 380–415 V global models on the same parallel bus. Country and array layout decide the model.
The L line runs on 3W+N+PE at 208 or 220 V, 50 or 60 Hz. Current is higher at the same power, so the inverter, the breakers and the cable sizes are chosen for that current rather than reused from a 400 V design.
At 208 V a 30 kW output draws about 83.3 A. At 220 V the same output draws about 78.7 A. Both figures drive the site's switchgear and the utility application.
Four Models Cover the Line
| Model | Power | Packs | Energy | Weight |
|---|---|---|---|---|
| BES-H30LX80 | 30 kW | 4 | 80 kWh | 1,025 kg |
| BES-H30LX100 | 30 kW | 5 | 100 kWh | 1,165 kg |
| BES-H30LX120 | 30 kW | 6 | 120 kWh | 1,303 kg |
| BES-H35LX120 | 35 kW | 6 | 120 kWh | 1,303 kg |
The packs are the same 314 Ah LFP cells used across the range, wired 1P20S. Adding a pack adds 20 kWh, which is why four, five and six packs map to 80, 100 and 120 kWh.
Two Inverters Match the Line
The HP3-30KL1 pairs with the 30 kW models and the HP3-35KL1 with the 35 kW model. Both are three-phase low-voltage units: 3W+N+PE, 120/208 V and 127/220 V, 50/60 Hz.
The inverter datasheet gives a maximum efficiency of 98.4% and a maximum AC output current of 97.2 A at 208 V and 91.9 A at 220 V. Size the protection on those numbers, not on the global 400 V figures.
Do not size a global inverter against these cabinets. A 400 V machine expects a different DC window and a different AC side, and the mismatch shows up as derating rather than as a clean fault.
Three MPPT Inputs Change the Array Plan
Each cabinet carries three MPPT inputs with a 150 to 850 V window and up to 55 A per tracker. The PV array sits between 60 and 70 kWp across the two models.
Compare that with the global line: five trackers, a 150 to 1000 V window and up to 120 kWp. Three trackers still let one roof with mixed orientations stay on separate strings, but the array size is set by the low-voltage roof, not by the cabinet.
Size the array from this datasheet, not from the global one. A 120 kWp plan copied over would exceed the 60–70 kWp DC limit, and the same strings would carry more current per tracker than the 55 A rating allows.
Numbers Do Not Convert Between Lines
A 380 to 415 V quote does not become a LatAm quote by changing a line. The power ratings, the inverter pairing, the current figures and the certification route all differ.
Nor does this page carry a global specification table. Sales confirms the market and the model before quoting, because the local grid code decides what can be connected.
Certification for Latin American markets is handled locally, market by market. Ask which documents exist for yours before the specification is fixed.
Questions about low voltage storage for Latin America
Is 220 V available as well as 208 V?
Yes. Both voltages are covered at 50 or 60 Hz, and the current figure differs between them.
Can I use the global 60 kW cabinet?
Not on a 208 or 220 V grid. The L line stops at 35 kW, and above that the design is parallel L units.
Which datasheet applies?
The L line datasheet. Ask for it by model, and check the DC window before the array is designed.
Does parallel operation work the same way?
The principle is the same. The current ratings and the switchgear differ, so the parallel plan is written for the L models.
Name the Country and the Voltage
The reply carries the L line datasheet, the model that matches your peak, and the documents that already exist for your market.