A cold room holds its temperature for a while after the power goes, and the backup only has to cover the gap until the supply returns or the product moves. The arithmetic is the compressor load in kW multiplied by the hours you need, with the motor start treated as a separate problem.

Published 2026-11-13

FIRST HOUR

What Happens in the First Hour of an Outage?

The compressors stop and the room starts to warm. The rate is set by the insulation, the door traffic and the thermal mass of the product inside. Nothing spoils in the first minutes. The clock that matters starts when the room crosses its limit.

That is why the requirement is written in hours rather than kilowatts. A site needs to know how long its room holds. That answer comes from its own panel, its own doors and its own stock rather than from a table.

Frozen stock and chilled stock behave differently. A freezer full of product has more thermal mass per cubic metre than a half-empty chill room. That is why a site's worst case is often a room that has just been loaded or just been emptied.

ARITHMETIC

How Much Backup Does a Cold Room Need?

Take the running kW of the compressors and multiply by the hours. A plant that draws 30 kW of compressor load for three hours needs 90 kWh of usable energy, which is exactly the BES-H50X100. The table below reads the same arithmetic across the range.

CabinetUsable energyAt 20 kWAt 30 kWAt 40 kW
BES-H37.5X80 / H40X8072 kWh3 h 36 min2 h 24 min1 h 48 min
BES-H49.9X100 / H50X10090 kWh4 h 30 min3 h 00 min2 h 15 min
BES-H60X120108 kWh5 h 24 min3 h 36 min2 h 42 min

The figures are arithmetic on usable energy at 90% depth of discharge. They assume the load is steady, and a real plant cycles its compressors. The honest method is to take the average draw over the window you are protecting.

MOTORS

Why Is a Compressor Harder to Back Up Than a Light?

A compressor starts with a current draw several times its running value, and that surge is what sizes the inverter rather than the steady load. The cabinet carries 150% of rated power for 10 seconds, which covers a normal start and not a locked rotor.

Two ways to make the start fit. Stagger the compressors so only one starts at a time. Or keep the existing soft starter or VFD in the circuit, so the surge never reaches the cabinet. Both are cheaper than buying power for a surge that lasts a second.

The VFD has its own behaviour to check. Many trip on undervoltage the moment the supply dips. A ride-through setting or a controlled stop belongs in the commissioning plan rather than in a later service visit.

CONFIGURATION

Which Configuration Keeps a Plant Running?

Put the essential board behind the cabinet. That board carries the compressors, controls, alarms and door heaters. Leave the non-essential loads on the grid side, because every kW on the backup side is window you give away. Start from the panel schedule.

  1. List the loads that must stay on, in kW, from the panel schedule.
  2. Separate the controls from the motors, because they have different tolerances.
  3. Check the single-phase share against 22 kW per phase for door heaters and lighting.
  4. Decide whether one cabinet covers the board or two cabinets share it.
  5. Test the whole board on the cabinet before the stock arrives, not after.

Above 60 kW the answer becomes parallel units. Ten cabinets give 600 kW and 4.8 MWh. A plant with several cold rooms usually finds one cabinet per room easier to operate than one large system with a shared board.

OTHER FAILURES

What Else Fails During an Outage?

The monitoring usually fails first. A plant that loses its alarm panel does not know the room is warming. The loss is discovered by a person walking in rather than by a phone message. Put the alarm and the network gear on the backup board.

Doors and defrost cycles come next. An automatic door that fails closed is a stock handling problem. A defrost cycle that starts during an outage dumps heat into a room nobody is cooling.

The cabinet itself reports. Smoke, temperature and water sensors sit inside it, along with an emergency stop. The string-level shutdown isolates a fault without taking the whole system down.

TEST

How Do You Plan the Test?

Test with product in the room and the compressors running. A test on an empty plant proves the wiring. It tells you nothing about the window at all, because the thermal mass is the part you are actually relying on.

Log the room temperature through the run, note when each compressor restarted, and compare the result with the arithmetic you used to size the cabinet. That comparison is the only evidence that the design assumption was right.

FAQ

Questions about this article

How long will a cold room hold without power?

It depends on the insulation, the door traffic and the stock inside, so no single figure applies. The panel and the room's own history give the answer, and the backup is then sized to cover that window plus a margin.

Can the cabinet start a compressor on its own?

Up to 150% of rated power for 10 seconds, which covers a normal direct-on-line start on a matched motor. For a larger motor, keep the soft starter or start the compressors in sequence.

What happens to the battery in a cold plant room?

The cabinet is rated for outdoor use with IP55 protection, and the performance warranty is written at 25 °C. A plant room well above that changes the cycle life, so the room temperature belongs in the design.

Do I need a generator as well?

Only if the outage is expected to outlast the battery window. A generator connected to the cabinet's generator input takes over the load while the battery covers the gap, and no external transfer switch is needed.

The Compressor Load and the Room Decide the Runtime.

Give us the running kW, the room type and the hours you need to hold. We come back with the cabinet, the start it can take and the board that should sit behind it.